100kW Low Water Temperature Chiller

7GP100CL-3

100kW Low Water Temperature Chiller

Choose an energy saving Performance Plus 100kW Heat Pump Water Heater to efficiently heat your swimming pool or spa using advanced Heat Pump technology.

Key Features

  • - Energy Efficient
  • - Environmentally friendly
  • - Easy operation
  • - Consistent performance from -10C to 45C
  • - Engineered and built in New Zealand from local and imported parts

Ideal Applications

  • - Low Water Temperature Water Chillers

kW out (chilling) 68
kW out Low Temp (chilling) 46
kW Input 20.0
Power Supply 3 Phase + N & E
Circuit Breaker - 3 Pole D Curve 63 amps
Nominal Compressor Run Amps 14.0/Phase (x2)
Fan Full Load Amps 1.70 (x4)
Operating temperature range (fresh water) 4°C to 35°C
Min.Flow Rate - Litre/Second 8.1
Water Connections Application Specific
Heat Pump Dimensions LxWxH ‐ mm 1755 x 1480 x 1390
Weight ‐ Kg 600
Air volume@ High Speed Litre/Sec 5,300
Sound Pressure Level , high dB(A) 63 / 64