The Titanium Series 7GP100HC-3v Heat and Chill is part of our Performance Plus range of models. It ensures a constant set temperature every time. Suitable for for heating and chilling water or brine.
Key Features
|
Ideal Applications
|
kW Output - Heating | 60 |
kW Output - Chilling | 68 |
kW Input | 20.0 |
Power Supply | 3 Phase + N & E |
Required D - curve circuit breaker amps | 63 amps |
Nominal compressor run amps | 15.2/Phase (x2) |
Fan full load amps | 2.37 (x2) |
Minimum flow rate - litre/second | 4.0 |
Water connections | Application Specific |
Dimensions LxWxH - mm | 2644 x 1380 x 2322 |
Weight - kg | 520 |
Air volume @ high speed litre/second | 8,000 |
Sound pressure level, high dB(A) | 66 |